Cat.6A U/UTP Cable 23AWG,PVC CM/CMR/CMP,LSZH |
|
|
Product Classification
Portfolio Albertsons@ Product Series ABS-Cat6A Product Type Twisted pair cable |
Cross Section Drawing
Construction Materials Jacket Material PVC / LSZH Conductor Material Bare copper Insulation Material Polyolefin
Dimensions Cable Length 305 m | 1000 ft Cable Weight 37.60 lb/kft Diameter Over Jacket, nominal 8.04 mm | 0.315 in Jacket Thickness 1.39 mm | 0.052 in
Electrical Specifications ANSI/TIA Category 6A dc Resistance Unbalance, maximum 3 % dc Resistance, maximum 7.6 ohms/100 m Mutual Capacitance at Frequency 6.0 nF/100 m @ 1 kHz Nominal Velocity of Propagation (NVP) 70 % Operating Frequency, maximum 500 MHz Operating Voltage, maximum 80 V Transmission Standards ANSI/TIA-568-C.2 | ISO/IEC 11801 Class EA Dielectric Strength, minimum 1500 Vac | 2500 Vdc
Environmental Specifications Environmental Space Non-plenum Flame Test Method CM / CMR / CMP Environmental Space Low Smoke Zero Halogen (LSZH) Smoke Test Method IEC 61034-2 Acid Gas Test Method IEC 60754-2 Flame Test Method IEC 60332-3 Installation Temperature 0 °C to +60 °C (+32 °F to +140 °F) Operating Temperature -20 °C to +60 °C (-4 °F to +140 °F)
General Specifications Cable Type U/UTP (unshielded) Packaging Type Reel Pairs, quantity 4 Cable Component Type Horizontal Jacket Color Light blue, Brown, Red. Lemon Green Conductor Gauge, singles 23 AWG Conductor Type, singles Solid Conductors, quantity 8
Mechanical Specifications Pulling Tension, maximum 11 kg | 25 lb
Standards Wire colour white - blue/bluewhite - orange/orangewhite - green/greenwhite - brown/brownin accordance with IEC 60189 and IEC 60708 (ring marked) PoE IEEE 802.3af Cat./Class Cat 6A / Class EA - limit values as specified by TIA/EIA 568-C & ISO/IEC 11801:2017 |